Chapter 3 _______________________________________________________________ Installation
VAISALA _______________________________________________________________________ 41
0507-024
Figure 25 Horizontal Mounting of Probe
Numbers refer to Figure 25 above:
1 = To be sealed.
2 = To be insulated.
3 = Insulate the cable.
4 = Let the cable hang loosely. This prevents condensed water
running to the sensor along the cable.
0507-022
Figure 26 Vertical Mounting of Probe
Numbers refer to Figure 26 above:
1 = To be sealed.
2 = Insulate the cable.
3 = To be insulated.
4 = Let the cable hang loosely. This prevents condensed water
running to the sensor along the cable.