511
HUMIDITY
HUMIDITY
9
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
2% WALL, DUCT AND OSA HUMIDITY TRANSMITTERS
H_20K SERIES
Accuracy 2% RH @ 73°F (23°C) from 5% to
90% RH; (0-5% & 90%-100%)
add 3%
Stability 0.5% drift per year
Thermal Effect 0.05% per °F
Supply Voltage 9.5-28 VDC
Signal Output 4-20 mA, thermistor, RTD
Maximum Output
Impedance 725Ω @ 24VDC
(Supply voltage - 9.5V) / 0.02
Measurement Range
RH 0-100%
Temperature -20° to 140°F (-29° to 60°C)
(see ordering information)
Sensor Protection
(Duct and OSA) Sintered filter
Operating Humidity 0-100% RH non-condensing
Operating Temperature -20° to 158°F (-29° to 70°C)
Enclosure
Room White plastic
Duct Weather resistant cast aluminum
Wiring Terminations Terminal block (22 to 16 AWG)
Weight
Room 0.3 lb (0.09 kg)
Duct 1.14 lb (0.52 kg)
OSA 1.2 lb (0.54 kg)
Approvals RoHs
Warranty 1.5 year
DESCRIPTION
The Kele Series H_20K Humidity Transmitters have been
specifically designed for use in HVAC/BAS applications.
These instruments measure relative humidity from 5% to
90% RH with 2% accuracy and produce a two wire 4-20 mA
linear output. All are available with an optional passive RTD or
thermistor. The duct and OSA versions may also be fitted with
a 4-20mA temperature transmitter.
FEATURES
• 2% accuracy (5% to 90%)
• Two-wire, 4-20 mA RH output
• Optional temperature thermistor
• Optional temperature RTD
• Optional temperature 4-20mA (duct or OSA)
APPLICATION
The temperature compensated circuitry converts the relative
humidity into a 4-20 mA signal. The optional temperature
sensors, RTDs or thermistors, offer direct connection to most
automation systems. On duct and OSA units, an optional 4-20
mA temperature transmitter may also be employed and is
rangeable from -30° to 250°F (-34° to 121°C).
DIMENSIONS
SPECIFICATIONS
HW20K
4.50
(11.43)
3.23
(8.20)
in
(cm)
(7.3)
4.625
(11.7)
(5.4)
7.0
(17.8)
0.25
(0.64)
HD20K
Foam gasket
5.25
(13.3)
4.43
(11.3)
2.88
(7.30)
2.125
(5.4)
1.25
(3.18)
HO20K
Komentarze do niniejszej Instrukcji