505
HUMIDITY
HUMIDITY
9
WE MAKE IT EASY.
kele.com 888-397-5353 USA
March 2014
ROOM OR DUCT HUMIDITY, TEMPERATURE, DEW POINT TRANSMITTER
EE23 SERIES
Accuracy
Humidity ±1.3%, ≤90% RH, 5° to 104°F
(-15° to 40°C)
Temperature ±0.27°F (±0.14°C)
Hysteresis < 2% RH
Supply Voltage
0-5 VDC: 10.5 - 35 VDC, 35 mA;
12 - 28 VAC, 0.8 VA
0-10 VDC: 15 - 35 VDC, 35 mA;
15 - 28 VAC, 1.4 VA
4-20 mA: 15 to 35 VDC, 60 mA;
15 to 28 VAC, 2.6 VA
Signal Output 4-20 mA, 0-5 VDC, 0-10 VDC
Maximum Output
Impedance 470Ω
Minimum Output
Impedance 5000Ω
Measurement Range Humdity: 0-100%
Sensing Technology Humidity: Capacitive, HC1000-200
Temperature: 1000Ω Platinum
(class A, DIN EN 60751)
Sensor Protection sintered stainless steel filter
Operating Temperature
Non-display -40° to 140°F (-40° to 60°C)
With display -22° to 140°F (-30° to 60°C)
Display LCD, English units
Enclosure Polycarbonate or Aluminum alloy
Enclosure Rating NEMA 4 (IP65)
Wiring Terminations Screw terminals maximum size wire
AWG 16 (1.5 mm2)
Approvals CE
Warranty 1 year
DESCRIPTION
The E+E EE23 series Humidity and Temperature
Transmitter has been developed for high-precision
measurement of relative humidity and temperature.
EE23 Series transmitters are available for wall and duct
mounting with or without the snap inmounting kit, which
allows a quick and easy exchange of the transmitter. Outputs
can be selected between voltage and current.
A special protection coating for the sensing element permits
the permanent use in very polluted environments.
FEATURES
• Humidity and temperature calibration
• NEMA 4 housing
• Stainless steel sintered filter
• Optional alarm switch
• Optional display
APPLICATION
• Green houses
• Storage rooms
• Swimming halls
• Meteorology
SPECIFICATIONS
Output and Supply
with active temperature output
with passive temperature output
Analog
outputs
Analog
output
Alarm Output
WIRING
Plastic:
Metal:
3.5 (9.0)
Both metal and plastic casings are 2.6" (6.7 cm) deep
2.6
(6.7)
5.3 (13.5)in
(cm)
3.5
(9.0)
DIMENSIONS
Komentarze do niniejszej Instrukcji