Chapter 6 ___________________________________________________________ Troubleshooting
VAISALA _______________________________________________________________________ 65
Error Codes
The transmitter has error codes that can be displayed on the serial line
using the
ERRS command. See section Display Currently Active Errors
on page 41.
Table 8 Error Codes
Error Code Error Message Possible Cause(s)
E1 Temperature sensor
open circuit/not calibrated
- Temperature sensor damaged
- Temperature sensor short circuit
- Temperature sensor missing
E2 Humidity sensor open
circuit/not calibrated
- Condensation on humidity sensor
- Humidity sensor damaged
- Humidity sensor short circuit
- Humidity sensor missing
E5 Capasitance out of range - Condensation on humidity sensor
- Humidity sensor damaged
E6 Program checksum error Internal error
E7 Parameter storage
checksum error
Internal error
E9 Sensor coefficient
checksum error
Internal error
E10 Current settings
checksum error
Internal error
E11 Factory settings
checksum error
Internal error
E12 Temperature sensor
values out of range
- Temperature sensor damaged
- Temperature sensor missing
E14 MeasTask not calculating
(ATEST)
This error may occurr when the
analog output is in test mode. See
page Test Analog Output on page
42.
E16 Default settings not found Internal error
E17 RH reading too high Internal error
E18 RH reading too low Internal error
E20 Log corrupted Internal error